Set.counter LE-01MQ&INTEGR wi-modbus-d
Product code: ME6752
Shipping costs are not included in the price.
Shipping costs are not included in the price.
Shipping & Returns
Master Energy | Master Investment Sp. z o.o.
1. Right of Return (14 Days)
Individual consumers (B2C) have the right to withdraw from the contract and return purchased items within 14 calendar days from delivery without stating a reason.
2. How to submit a return or claim?
- 📧 E-mail: bok@masterenergy.eu
- 📞 Phone: +48 884 570 201
- 🏢 Registered Address: Master Investment Sp. z o.o., Rondo ONZ 1, 00-124 Warsaw, Poland (VAT ID: PL7010345632)
3. Complete terms and conditions
Detailed freight information, pallet shipping methods, and B2B commercial terms are available at our dedicated information page:
Payment methods
Ask about the product
Administratorem danych osobowych jest Master Investment sp. z o.o.. Przetwarzamy je w celu przesłania odpowiedzi na zapytanie. Więcej informacji dotyczących przetwarzania danych osobowych znajduje się w polityce prywatności.
Description
LE-01MQ is a single-phase electronic energy meter with bidirectional measurement and network parameter analysis. The device records active and reactive energy (import/export), instantaneous values (voltage, current, power, apparent power, reactive power, power factor), frequency, and maximum power demand. It is equipped with two pulse outputs and an RS-485 communication port with Modbus RTU protocol support, enabling remote reading and integration into the measurement network.
Manufacturer information
Manufacturer: F&F Filipowski sp.j., based in Pabianice (Konstantynowska 79/81). The company supplies the device under the designation LE-01MQ and provides technical documentation and service support. The instruction includes the certificate number and compliance with directives and warranty information.
Electrical and functional parameters
- Measurement system: 1P2W – single-phase 2-wire (230 V + N).
- Reference voltage: 230 V AC (range 176–276 V AC).
- Frequency: nominally 50 Hz (accepted 50/60 Hz ±2%).
- Current: Ib = 5 A, Imax = 100 A, Imin = 0.25 A, start current 0.4% Ib.
- Active / reactive / apparent power: measurement of active (W), reactive (Var) and apparent (VA) power with an accuracy of ±1% of the maximum range (for power) and ±1% IEC 62053-21 for active energy.
- Accuracy class: class B (detailed accuracies: voltage 0.5% of max range, current 0.5% of nominal, frequency 0.2% mid-range, cosφ 1% unity).
- Energy: records imported/exported active energy and reactive energy import/export; total energy available in registers.
- Pulse outputs: 2 x OC (open collector) 27 V DC / 27 mA; output 1 programmable for kWh/kVarh with pulse constant selection (1/10/100/1000) and pulse width (60/100/200 ms); output 2 fixed for kWh (3200 pulses/kWh) with a width of 200 ms.
- Communication: RS-485 with Modbus RTU; network address 1–247; transmission speeds 1200/2400 (default)/4800/9600 bps; parity NONE/ODD/EVEN; stop bits 1/2.
Mechanical and environmental parameters
- Mounting: on DIN rail.
- Housing: self-extinguishing material UI94 V-0.
- Protection class: IP51 (inside the housing).
- Operating temperature: -25 ÷ 55°C; storage temperature: -40 ÷ 70°C.
- Relative humidity: 0 ÷ 95% without condensation.
- Installation category and mechanical environment: CAT II, M1, pollution degree E2.
- Anti-tampering protections: terminal blocks with sealing options; laser-engraved serial number.